Plumbing tools

AS/NZS 3500.1:2025 Water services · Section 3 and Appendices C and D

What are you sizing?

Pressure and length

Use the minimum pressure from the water supplier (Cl 3.3.1). The outlet needs at least 50 kPa, which is 5 m head (Cl 3.3.2). Some fixtures need more, so raise it if the maker says so.

Pipe sections

Work back from the furthest outlet. For each section, enter everything it supplies downstream.

Result

SectionLUFlow L/sSizeCarries L/sVelocity m/s

How this is worked out

This follows the sizing method in AS/NZS 3500.1 Appendix C (supply to dwellings, using the probable simultaneous demand in Table 3.2.3) and Appendix D (inside a dwelling, using loading units from Table 3.2.1 converted with Table 3.2.4).

Pressure drop = minimum head at the main − height of the highest outlet − head needed at the outlet (Equation D.2). The pressure-drop table is the next one down, and the index-length column is the next one up, as in Steps 7 and 8 of C.2.

For copper, pipe capacities are read straight from Table C.1, so the answer matches the book. For other pipes, the app uses Equation C.1 (the equation Table C.1 is built from, with a 1.5 factor for fittings) with that pipe's internal diameter from Appendix A, capped so velocity stays at or under 3.0 m/s (Cl 3.4).

Appendices C and D are informative quick-sizing methods. A full hydraulic calculation may give a different answer. Check the job's requirements and the supplier's pressure data.