Plumbing tools

AS/NZS 3500.1:2025 Water services · AS/NZS 3500.2:2025 Sanitary plumbing and drainage

What's on the job?

Tap + or − for how many of each fixture there are.

Pressure and length

More settings

5 m (50 kPa) is the minimum at any outlet (Cl 3.3.2). Raise it if a fixture needs more.

Use the minimum pressure from the water supplier (Cl 3.3.1).

Result

PipeFlow L/sSizeCarries L/sm/s

How this is worked out

This follows the quick-sizing method in AS/NZS 3500.1 Appendices C and D. For one house, the loading units of every fixture are added up (Table 3.2.1) and converted to a flow (Table 3.2.4) to size the main line. It is never less than the 0.48 L/s minimum for a dwelling (Table 3.2.3). Each fixture's branch is sized on that fixture's own flow (Table 3.2.1). For units or several houses, the shared supply line uses Table 3.2.3.

Pipe runs between groups of fixtures (for example, a line feeding just the bathroom) carry less than the main and can sometimes be one size smaller. Size those by adding up just the fixtures they feed.

Pressure drop = minimum head at the main − height of the highest outlet − head needed at the outlet (Equation D.2). The pressure-drop table is the next one down, and the index-length column is the next one up, as in Steps 7 and 8 of C.2.

For copper, pipe capacities are read straight from Table C.1, so the answer matches the book. For other pipes, the app uses Equation C.1 (the equation Table C.1 is built from, with a 1.5 factor for fittings) with that pipe's internal diameter from Appendix A, capped so velocity stays at or under 3.0 m/s (Cl 3.4).

Appendices C and D are informative quick-sizing methods. A full hydraulic calculation may give a different answer. Check the job's requirements and the supplier's pressure data.