AS/NZS 3500.1:2025 Water services · AS/NZS 3500.2:2025 Sanitary plumbing and drainage
Tap + or − for how many of each fixture there are.
Sizes the shared supply line using the flow for that many dwellings (Table 3.2.3).
5 m (50 kPa) is the minimum at any outlet (Cl 3.3.2). Raise it if a fixture needs more.
Use the minimum pressure from the water supplier (Cl 3.3.1).
| Pipe | Flow L/s | Size | Carries L/s | m/s |
|---|
This follows the quick-sizing method in AS/NZS 3500.1 Appendices C and D. For one house, the loading units of every fixture are added up (Table 3.2.1) and converted to a flow (Table 3.2.4) to size the main line. It is never less than the 0.48 L/s minimum for a dwelling (Table 3.2.3). Each fixture's branch is sized on that fixture's own flow (Table 3.2.1). For units or several houses, the shared supply line uses Table 3.2.3.
Pipe runs between groups of fixtures (for example, a line feeding just the bathroom) carry less than the main and can sometimes be one size smaller. Size those by adding up just the fixtures they feed.
Pressure drop = minimum head at the main − height of the highest outlet − head needed at the outlet (Equation D.2). The pressure-drop table is the next one down, and the index-length column is the next one up, as in Steps 7 and 8 of C.2.
For copper, pipe capacities are read straight from Table C.1, so the answer matches the book. For other pipes, the app uses Equation C.1 (the equation Table C.1 is built from, with a 1.5 factor for fittings) with that pipe's internal diameter from Appendix A, capped so velocity stays at or under 3.0 m/s (Cl 3.4).
Appendices C and D are informative quick-sizing methods. A full hydraulic calculation may give a different answer. Check the job's requirements and the supplier's pressure data.
Tap + or − for everything that drains into this pipe.
A washing machine that empties into the laundry trough, or a dishwasher on the sink trap, doesn't count separately: only the trough or sink counts (Table 6.3(A) Note 1).
Use a minus number if the ground rises along the run.
| Size | Max FU at this grade | OK? |
|---|
Fixture units come from AS/NZS 3500.2 Table 6.3(A). The drain size is the smallest size whose maximum fixture unit loading at your grade (Table 3.3.1) is at least the total. If your grade falls between two rows of the table, the next flatter row is used, which is the safe side.
Minimum grades are from Table 3.4.1. Grades flatter than that are reduced grades (Cl 3.4.2) and need the minimum fixture units in Table 3.4.2 if soil fixtures are connected; otherwise a way of flushing the drain is needed.
Depth of cover is from Table 3.7.2, measured from the top of the pipe socket or inspection opening to the finished surface. The depth check here uses the pipe's outside diameter, so allow a little more for sockets.